  • Summary:
    In this paper, an auto-tuning AR (area ratio) ejector and an auto-tuning NXP (nozzle exit position) ejector are designed to solve the contradictions between the fixed structure and the dynamic primary pressure driven by multi-condition low-grade heat energy. A CFD (Computational Fluid Dynamics) model is used to calculate the performance of the ejector under different operational conditions. The effects of both AR and NXP on the performance of the ejector are systematically studied. The optimal area ratio increases linearly along with the primary pressure, and the optimum NXP decreases as the p